浔之漫智控技术(上海)有限公司-西门子总部
西门子电源模块代理商 , 西门子一级总代理商 , 西门子模块一级代理商
西门子CPU通讯模块代理商
发布时间:2023-09-19
观看西门子CPU通讯模块代理商视频:
概述

The CPU for standard and fail-safe applications with medium/high re for program/data storage in the S7-1500 Controller product range

Can be used for safety functions up to SIL 3 according to IEC 61508 and up to PLe according to ISO 13849

High processing speed for binary and floating-point arithmetic

Used as central PLC in production lines with central and distributed I/O

Supports PROFIsafe in centralized and distributed configuration 

PROFINET IO IRT interface with 2-port switch

PROFINET IO controller for operating distributed I/O on PROFINET

PROFINET I-Device for connecting the CPU as an intelligent PROFINET device under a SIMATIC or non-Siemens PROFINET IO controller

Isochronous mode

Note:
SIMATIC Memory Card required for operation of the CPU

应用

The CPU 1513F-1 PN is the CPU with a medium to large program and data memory for standard and fail-safe applications that also contain distributed automation structures alongside central I/O. It can be used as a PROFINET IO controller or as distributed intelligence (PROFINET I-Device). The integrated PROFINET IO IRT interface is designed as a 2-port switch, enabling a linear topology to be set up in the system. In addition, the CPU offers comprehensive control functionalities as well as the ability to connect drives via standardized PLCopen blocks.

设计

The CPU 1513F-1 PN has:

A powerful processor:
The CPU achieves a command execution time as low as 40 ns per binary command.

Extensive work memory:
450 KB for program, 1.5 MB for data

SIMATIC Memory Cards as load memory;
permit additional functions such as Datalog and Archive Flexible

Expansion capability:
single-tier configuration with max. 32 modules (CPU + 31 modules)

Display with functions for

Display of overview information such as station name, higher level designation, location designation, etc.

Showing diagnostic information

Showing module information

Showing display settings

Setting IP addresses

Setting date and time

Switching the operating mode

Resetting the CPU to factory settings

Disabling/enabling the display

Enabling of protection levels

Display of safety mode, overall signature and date of the last download with signature change

PROFINET IO IRT interface for connecting distributed I/O via PROFINET

Supports PROFIsafe in centralized and distributed configuration

功能

Performance

Faster command processing, depending on the CPU type, language extensions and new data types

Even shorter response times of the CPUs due to considerably faster backplane bus

Powerful network connection:
Each CPU is e with PROFINET IO IRT (2-port switch) as standard interface.

Integrated technology

Connection of analog and PROFIdrive-capable drives via standardized blocks (PLCopen)

Support of speed-controlled and positioning axes as well as external encoders

Trace functions for all CPU tags, both for diagnostics in real time and for sporadic error detection

Comprehensive control functionalities, e.g. easily configurable blocks for automatic optimization of the control parameters for optimum control quality

Security Integrated

Password-based know-how protection against unauthorized read-out and modification of program blocks

Copy protection for tying individual blocks to the serial number of the SIMATIC Memory Card: The block can only run if the configured memory card is inserted in the CPU.

4-level authorization concept:
Communication to operator panels can also be restricted.

Manipulation protection:
The controller recognizes changed or unauthorized transmissions of the engineering data.

Design and handling

Display of overview information:
E.g. Station name, plant designation, location identifier, etc., diagnostic information, module information, display settings.

Possible operations on the display:
Set addresses, set date and time, select operating mode of CPU, reset CPU to factory settings, disable/enable display, activate protection levels.

Integrated system diagnostics

System diagnostics information is displayed consistently and in plain text in the display, TIA Portal, operator panels and web server, even for messages from the drives, and updated even if the CPU is in STOP mode.

Integrated in the firmware of the CPU, no special configuration is required

SIMATIC Memory Card (required for operation of the CPU)

Used as plug-in load memory or for updating the firmware.

Also for storing additional documents or csv files (for recipes and archives)

Creation of data blocks for storage/reading of data via SFCs of the user program

Datalog (archives) and recipes

Storage of csv files for recipes and archives on the SIMATIC Memory Card;
easy access to plant-relevant operating data using Office tools and via web server

Easy access to configuration data of the machine by means of a web browser or SD card reader (two-way data exchange from and to the PLC)

Programming of the standard program section

Programming as of STEP 7 V12 SP1

Programming of the fail-safe program section

Programming of the safety-related program section with the "STEP 7 Safety Advanced" option package. STEP 7 Safety Advanced V12 can run under SIMATIC STEP 7 Professional V12 SP1.

技术规范

Article number

6ES7513-1FL02-0AB0

CPU 1513F-1 PN, 450KB Prog., 1,5MB data

General information

Product type designation

CPU 1513F-1 PN

HW functional status

展开全文